Rate Energy (kWh) | 7311.36 | 5176 | 2534 |
Battery Cell | Square Aluminum Case Cells 280Ah |
Short Blade 280Ah | Flat 500Ah |
System Grouping Mode | PACK: 1P24S; Battery cluster: 17S; Battery Cabin: 2 |
PACK: 1P30S, 1P10S; Battery Cluster (13+1) P; Battery Cabin: 14 |
Battery Cluster: 1P198S; Battery Cabin: 8P |
Rated Voltage(V) | 1305.6 | 1280 | 633.6 |
Working Voltage(V) | 1142.4~1346.4 | 1120~1440V | 495-722.7 |
System Rated Power (kW) | 3655 | 2500 | 1267 |
Cycle Life | ≥6000 times (80%DOD, 0.5C,@25℃) |
≥6000 times (80%DOD, 0.5C,@25℃) |
≥6000 times (80%DOD, 0.5C,@25℃) |
DC System Efficiency | ≥93% (0.5C/0.5C,@25℃) | ||
Operating Temperature (℃) | Charge: 0~55; Discharge: -30~55 | ||
Container Type | 40ft HQ 45ft HQ 30ft HQ | ||
Fire Fighting System | Heptafluoropropane/perfluorohexanone | ||
Balanced Mode | Active equilibrium/passive equilibrium | ||
Altitude | ≤3000m (3000m need to be derated use) | ||
Thermal design | Forced air cooling | ||
Application Scenario | Peak cutting and valley filling, emergency power supply, new energy consumption, power support, peak regulation and frequency regulatiation. |